Commands Reference
CoolMaster PRM
16
www.coolautomation.com
© 2011 Cool Automation LTD
Rev 3.8
EXIT CODE
Request Successfully Executed
Unit with specified UID not found
COMPATIBILITY
This command is obsolete and is supported only for backward compatibility.
EXTENSIONS
CoolMaster 4000F PAC-YG Support
In CoolMaster 4000F v2.5.6 or higher for PAC-YG66 (digital I/O extender) and PAC-YG63 (analog I/O
extender), stat,stat2,stat3 commands output format will differ from the mentioned above.
· PAC-YG66. CoolMaster 4000F v2.5.6
>stat 012
012 DIG IN:001111 OUT:000001 OK
OK
PAC-YG66 Centralized Address
6 Digital inputs 1-6 status. X can be 0 or 1
6 Digital outputs 1-6 status. X can be 0 or 1
· PAC-YG63. CoolMaster 4000F v2.5.6
>stat 011
011 ANA 007.5 278.8 OK
OK
PAC-YG63 Centralized Address
4.1.16 stat2
SYNOPSIS
stat2 [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units. stat2 compared to stat1 has additional Filter Reset
Sign indication
EXAMPLE
>stat2
100 ON 12C 12,41C High Cool OK 0