10 Entek 9000 Series Sensor Installation Guide
Sensor Cable Guidelines
Cable Installation
The cable from the sensor is a critical component in getting the signal to the monitoring
device. The 2-wire cables with shield listed below are dedicated, one per sensor, to carry
sensor signals to the monitoring device.
Cable run at
10 kHz
Maximum
attenuation
No. of
channels/
cable
Cable
diam.
Belden
No.
Max.
Tem p.
Alpha
No.
Up to 500 ft
(152 m)
6 dB (2:1) 1 0.168 in
4.27 mm
8641 140° F
60° C
2400C
Up to 500 ft
(152 m)
12 dB (4:1) 1 0.175 in
4.45 mm
8761 140° F
60° C
2401C
3 0.310 in
7.87 mm
8777 176° F
80° C
6010C
6 0.390 in
9.91 mm
8778 176° F
80° C
6012C
12 0.480 in
12.2 mm
9768 176° F
80° C
6017C
Up to 1000 ft
(304 m)
6 dB (2:1) 3 0.370 in
9.40 mm
9730 140° F
60° C
6073C
6 0.480 in
12.12 mm
9731 140° F
60° C
6076C
Up to 1500 ft
(457 m)
12 dB (4:1) 12 0.660 in
16.7 mm
9734 140° F
60° C
6079/
12C
Cable run at
10 kHz
Maximum
attenuation
No. of
channels/
cable
Cable
diam.
Belden
No.
Max.
Tem p.
Alpha
No.
Up to 4000 ft
(1219 m)
6 dB (2:1) 1 0.204 in
5.18 mm
8762 140° F
60° C
2411C
3 0.340 in
8.64 mm
9873 176° F
80° C
6033C
6 0.430 in
10.9 mm
9874 176° F
80° C
6036C
12 0.590 in
15.0 mm
9877 176° F
80° C
6042C