Connecting 9000 Series Sensors to Monitors
Entek 9000 Series Sensor Installation Guide 17
16
18
19
24
23
20
21
22
17
7
10
15
11
12
13
14
9
8
2
6
4
5
3
1
43
44
48
45
46
47
32
42
35
38
41
40
39
36
37
34
33
31
29
30
27
28
26
25
Common
Channel 1 Signal
Note: IEPE transducers require constant current diodes attached to the backplane,
one per active channel. Refer to Reference Drawing A39588+ for E39588 constant
current diode assembly.
Shield
Ground at 6600 monitor rack
Pin A - Signal
Pin B - Common
Cable shield not
connected at this end
6600 Monitor Pin Inputs
Pin 1 Channel 1 Input Signal
Pin 2 Signal Common
Pin 3 Channel 2 Input Signal
Note: If shield is connected at the transducer, do not
ground the shield at the 6600 monitor end. If shield
connection is unknown at the two pin connector,
ohm out and verify before wiring.
CONNECTING 9000 SERIES TRANSDUCERS TO A 6600 MONITOR
Common
Channel 2 Signal
Cable shield not
connected at this end
Shield
Ground at 6600 monitor rack